Plan Review Notes
Plan Review Notes For Permit 99070921
Permit Number 99070921
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1) EXHAUST HOOD TERMINATION TO BE MIN.
 40" ABOVE ROOF.
 2) MINIMUM SLOPE FOR EXHAUST DUCT TO BE
 1 INCH PER FOOT PER 1994 SMC 505.4
 3) CLEANOUTS TO BE PER 1994 SMC 505.5.1
 4) CLEARANCE TO INSIDE OF ENCLOSURE FROM
 DUCT TO BE MIN. 6" PER 1994 SMC 505.9