Plan Review Notes
Plan Review Notes For Permit 99070917
Permit Number 99070917
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHT.C-2-SHOW HORIZONTAL DISTANCE BETWEEN
 WATER SERVICE AND SANITARY SEWER .COMPLY
 W/SPC SEC.608.3.
  
 CLEANOUTS IN BUILDING SEWER SHALL BE ED
 SPACED PER SPC SEC.710.2.4(2).
  
 SHT.A2.1-SINKIN LOUNGE SHALL COMPLY W/
 F.A.C.B.C. SECS.4.24.1- 4.24.7.
  
 DRINKING FOUNTAIN SHALL COMPLY W/
 F.A.C.B.C. SEC.4.1.3.(10)(A).
  
 SHOW OCCUPANT LOAD TO ENSURE COMPLIANCE
 W/TABLE 407 OF SPC.
  
 MAIN VENT REQ'D.FORSANITARY SYSTEM.
 SIZE SHALL COMPLY W/SPC SEC.904.3.1 AND
 RUN UNDIMINISHED IN SIZE THRU ROOF.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.2.