| Plan Review Notes For Permit 99070917 |
| Permit Number |
99070917 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED | | | | | | 1) ALL DUCTWORK IN UNCONDITIONED SPACES | | | TO BE MIN. 1 1/2INCH(R-6) SUPPLY AND | | | RETURN | | | 2) PROVIDE REFRIGERANT QUANTITY CALCULA- | | | TIONS TO SHOW COMPLIANCE W/ 1997 SMC | | | CHAPTER 11 |
|