Plan Review Notes
Plan Review Notes For Permit 99070898
Permit Number 99070898
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-SOIL TEST REPORT INDICATES SOME AREAS
 HAVE ORGANIC MATERIALS.INSPECT LOCATION
 WHERE HOUSE IS GOING TO BE BUILT AND
 REMOVE AND REFILL AREA IF REQUIRED.
 2-FLOOD ZONE A0. PROVIDE ELEVATION
 CERTIFICATE.
 3-PROVIDE UPDATE PRODUCT APPROVAL AND
 COPY OF TESTING AS PER CHAPTER 17 SBC
 1997 FOR NORANDEX ALUMINUM MULLIONS,
 FIXED WINDOWS,SINGLE HUNG WINDOWS AND
 SLIDING GLASS DOORS.
 4-UPDATE DESIGN CERTIFICATION FOR BLDG
 CODE COMPLIANCE FORM. SBC 1997.
 NOTE: THIS FORM IS NOT REQUIRED IF ALL
 THE INFORMATION IS SPECIFIED ON PLANS.
 5-STORM PANELS: PROVIDE COMPLETE
 INSTALLATION SCHEDULE AND KEY PLAN AS
 PER CITY POLICY. SEE ATTACHED.
 STORM SHUTTERS TO BE UNDER A SEPARATE
 PERMIT.
 6-PROVIDE CURRENT PRODUCT APPROVAL FOR
 ENTRY DOOR. IT'S EXPIRED.
 7-REVISE ENGINEERED TRUSS DRAWINGS.
 *DESIGN CRITERIA SHALL STATE THE
 SPECIFIC YEAR OF SBC USED. 1997.
 *SOME TRUSSES ARE DESIGNED USING SBC
 AND SOME TRUSSES ARE DESIGNED USING
 ASCE-7-93. REVISE AS REQUIRED. DESIGNER
 OF RECORD IS USING SBC.
 *ENGINEERED TRUSS C-3 IS MISSING.
 *DESIGNER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS AFTER CORRECTIONS ARE DONE.