| 2001-03-19 00:00:00 | *****************DENIED***************** | | | | | | INSUFFICIENT INFORMATION - PLEASE | | | PROVIDE INFORMATION ON FIRE DAMPERS | | | ON DUCTS PENETRATING RATED WALLS, | | | CEILINGS AND FLOORS (1997 SMC 610.1.2 | | | AND 610.2).ALSO, SPECIFIC | | | LOCATION AND INSTALLATION DETAILS OF | | | EACH FIRE DOOR, DAMPER, CEILING DAMPER | | | AND SMOKE DAMPER SHALL BE SHOWN AND | | | PROPERLY IDENTIFIED ON PLANS. |
|