Plan Review Notes
Plan Review Notes For Permit 99070895
Permit Number 99070895
Review Stop M
Sequence Number 2
Notes
Date Text
2001-03-19 00:00:00*****************DENIED*****************
  
 INSUFFICIENT INFORMATION - PLEASE
 PROVIDE INFORMATION ON FIRE DAMPERS
 ON DUCTS PENETRATING RATED WALLS,
 CEILINGS AND FLOORS (1997 SMC 610.1.2
 AND 610.2).ALSO, SPECIFIC
 LOCATION AND INSTALLATION DETAILS OF
 EACH FIRE DOOR, DAMPER, CEILING DAMPER
 AND SMOKE DAMPER SHALL BE SHOWN AND
 PROPERLY IDENTIFIED ON PLANS.