| Date |
Text |
| 2001-02-28 00:00:00 | DENIED; |
| | |
| | 1.P100.1 (AIR CHAMBER DETAIL) SHALL |
| | COMPLY WITH 94 SPC 607.8.2 AND 607.8.3 |
| | ENGINEERED AIR CHAMBERS MUST BE SIZED |
| | AND ACCESSIBLE. PROVIDE MANUFACTOR |
| | SPECIFICATIONS. |
| | 2.WATER SERVICE DETAIL; REDUCED PRESSURE |
| | DEVICE IS REQUIRED BY WPB WATER DEPART |
| | MENT. CONTACT ORVAL POLK FOR LOCATION. |
| | |
| | 3.GREASE INTERCEPTOR P101.2 SALL BE |
| | REVIEWED BY RODNEY COMPO 835-7423 |
| | WASTE ORD.#2938-96. |
| | 4.(TRAP RESEAL DIAGRAM) NOTE 3. SUPPLY |
| | MANUFACTORS CUT SHEET WITH INFORMATION |
| | ON TRAP PRIMERS TO BE USED. |
| | 5.BOTTOM FED WATER HEATER SHALL HAVE A |
| | VACUUM RELIEF VALVE INSTALLED. SPC |
| | 507.1.2. |
| | 6.UNIONS ON WATER HEATER DETAIL MUST BE |
| | DIELECTRIC. |
| | 7.P401.4 ELEVATOR SUMP PUMP MUST GO TO A |
| | HOLDING TANK. DISCHARGE MUST STAY ON |
| | PROPERTY. NOT PERMITED TO TIE INTO |
| | SANITARY. |
| | 8.LENGTH OF SANITARY VENT SYSTEM IS |
| | LONGER THAN ALLOWED BY TABLE 920.2. |
| | 9.ROOF DRAIN PIPING DETAIL AND ISOMETRIC |
| | DIAGRAM REQUIRED, TO COMPLY WITH SPC |
| | CHAPTER 11. SHOW SQ. FT. PER DOWN |
| | SPOUT. |
| | 10.(A702) FIRST AID DEPARTMENT; BATHROOM |
| | DOORS ARE NOT PERMITED TO OPEN INTO |
| | THE CLEAR FLOOR SPACE OF A HANDICAP |
| | FIXTURE. FACBC 4.17.5 |
| | 11.WOMANS GANG BATHROOMS MUST COMPLY |
| | WITH FACBC 4.22.4. OUTWARD SWING DOOR |
| | AND GRAB BARS ON AN ADDITIONAL STALL |
| | OVER 6. |
| | 12.HANDICAP DRESSING ROOMS SHALL COMPLY |
| | WITH FACBC 4.35 THRU 4.35.5.SHOW |
| | DETAIL DRAWING. |
| | 13.BACKFLOW PROTECTION REQUIRED FOR |
| | DOMESTIC WATER AT POOL AND FOUNTAINS. |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |
| | 659-8096 EXT. 8377 |