Plan Review Notes
Plan Review Notes For Permit 99070843
Permit Number 99070843
Review Stop P
Sequence Number 5
Notes
Date Text
2001-02-28 00:00:00DENIED;
  
 1.P100.1 (AIR CHAMBER DETAIL) SHALL
 COMPLY WITH 94 SPC 607.8.2 AND 607.8.3
 ENGINEERED AIR CHAMBERS MUST BE SIZED
 AND ACCESSIBLE. PROVIDE MANUFACTOR
 SPECIFICATIONS.
 2.WATER SERVICE DETAIL; REDUCED PRESSURE
 DEVICE IS REQUIRED BY WPB WATER DEPART
 MENT. CONTACT ORVAL POLK FOR LOCATION.
  
 3.GREASE INTERCEPTOR P101.2 SALL BE
 REVIEWED BY RODNEY COMPO 835-7423
 WASTE ORD.#2938-96.
 4.(TRAP RESEAL DIAGRAM) NOTE 3. SUPPLY
 MANUFACTORS CUT SHEET WITH INFORMATION
 ON TRAP PRIMERS TO BE USED.
 5.BOTTOM FED WATER HEATER SHALL HAVE A
 VACUUM RELIEF VALVE INSTALLED. SPC
 507.1.2.
 6.UNIONS ON WATER HEATER DETAIL MUST BE
 DIELECTRIC.
 7.P401.4 ELEVATOR SUMP PUMP MUST GO TO A
 HOLDING TANK. DISCHARGE MUST STAY ON
 PROPERTY. NOT PERMITED TO TIE INTO
 SANITARY.
 8.LENGTH OF SANITARY VENT SYSTEM IS
 LONGER THAN ALLOWED BY TABLE 920.2.
 9.ROOF DRAIN PIPING DETAIL AND ISOMETRIC
 DIAGRAM REQUIRED, TO COMPLY WITH SPC
 CHAPTER 11. SHOW SQ. FT. PER DOWN
 SPOUT.
 10.(A702) FIRST AID DEPARTMENT; BATHROOM
 DOORS ARE NOT PERMITED TO OPEN INTO
 THE CLEAR FLOOR SPACE OF A HANDICAP
 FIXTURE. FACBC 4.17.5
 11.WOMANS GANG BATHROOMS MUST COMPLY
 WITH FACBC 4.22.4. OUTWARD SWING DOOR
 AND GRAB BARS ON AN ADDITIONAL STALL
 OVER 6.
 12.HANDICAP DRESSING ROOMS SHALL COMPLY
 WITH FACBC 4.35 THRU 4.35.5.SHOW
 DETAIL DRAWING.
 13.BACKFLOW PROTECTION REQUIRED FOR
 DOMESTIC WATER AT POOL AND FOUNTAINS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377