| Plan Review Notes For Permit 99070843 |
| Permit Number |
99070843 |
|
| Review Stop |
FIRE |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-07-16 00:00:00 | 1) KNOX-BOXES WILL BE REQUIRED AT | | | VEHICULAR GATES. | | | | | | 2) OPENINGS THRU SECURITY GATES MUST | | | BE AT LEAST TWENTY (20) FEET IN CLEAR | | | WIDTH IN WHICH FIRE RESCUE VEHICLES | | | ARE EXPECTED TO PASS THRU. | | | | | | 3) BUILDING ADDRESS IS REQUIRED WITH | | | AT LEAST SIX (6) INCH HIGH NUMERALS. | | | YARD SIGN SHOULD DISPLAY ADDRESS SINCE | | | THE BUILDING SITS SO FAR OFF THE ROAD | | | UNLESS AN ALTERNATIVE LOCATION IS | | | AGREED UPON. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|