| Plan Review Notes For Permit 99070843 |
| Permit Number |
99070843 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-06-17 00:00:00 | ******************* UNSAT ************* | | | 1)NOTE: PLEASE NOTE THAT PLANS SUBMITTED | | | AS "AS-BUILTS" ARE NOT COMPLETE. | | | PLEASE NOTE PANEL SCHEDULE THAT ARE NOT | | | COMPLETE. | | | PLEASE NOTE RISER DIAGRAM IS SUBMITTED | | | AS COMPLETE AND THERE IS A MISSING SEC | | | THAT GOES WITH E 902? PLEASE NOTE THAT | | | THE ONE- LINE SHOWN ON E902.1 IS MISSING | | | SOME ITEMS THAT ARE SHOW ON OTHER RISER | | | PLEASE CORRELATE AND COMPLETE PLANS FOR | | | SUFFICENT ELECTRICAL REVIEW. | | | | | | 2)NOTE: PLEASE NOTE THAT THERE ARE SOME | | | PANELS/DIST PANELS ON THE LOAD SIDE | | | OF TRANSFORMERS THAT HAVE NO MAINS | | | SHOWN? PLEASE SEE 240-21 FOR TERMINATION | | | IN A SINGLE SET OF OCP. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|