Plan Review Notes
Plan Review Notes For Permit 99070843
Permit Number 99070843
Review Stop B
Sequence Number 4
Notes
Date Text
2001-02-20 00:00:00REVISIONS DATED 1/5/01
 THE SMALL MEETING ROOM SHOWN ON SHEET
 A201.4 DOES NOT HAVE THE EXIT DOORS A
 DISTANCE APART EQUAL TO OR GREATER THAN
 1/2 THE DIAGONAL DISTANCE OF THE ROOM
 AS REQUIRED BY SBC 1004.1.4.PLEASE
 REVISE AS NECESSARY.
  
 SECTION 3/A505.SHOW THE DESIGN LOADS
 FOR THE CATWALK.SEE SBC 1604.8.
  
 THE DOOR SCHEDULES DO NOT SHOW RATED
 ENTRANCE DOORS FOR THE APARTMENTS.SEE
 SBC 704.1.1 AND SBC 705.1.2
  
 SHEET A203 DOES NOT CLEARLY SHOW THE
 AISLE AND SEATING DIMENSIONS, OR
 PLACEMENT OF HANDRAILS TO DETERMINE
 COMPLIANCE WITH SBC 1019.9 AND SBC
 1019.10.
  
 THE RISER MOUNTED SEATING MUST COMPLY
 WITH SBC 1019.10.3.2. FOR ROWS HAVING >
 14 SEATS.
  
 SEE SBC 1007.5.7 FOR THE HANDRAIL
 SPACING REQUIREMENTS ON THE VOMITORY
 STAIRS.
  
 PERMIT FEES MUST BE PAID TO THE CITY FOR
 THE NEW AND ADDED WORK.
  