| Plan Review Notes For Permit 99070843 |
| Permit Number |
99070843 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CONTINUATION OF PLAN REVIEW NOTES OF | | | REV.2- 10/12/99. | | | | | | LINE SIZES FOR BLDG.DRAIN AND BLDG.SEWER | | | DON'T CORRELATE BETWEEN SHTS.P-8 & P-2. | | | AND DRAIN LINES ON P-8 DON'T MATCH P-5. | | | | | | SIZE ALL SECTIONS OF THE SANITARY | | | ISOMETRIC.SPC 104.2.1. | | | | | | MAX.4 FIXTURES PERMITTED TO BE CONNECTED | | | TO 1/2" H.W.-COUNTYWIDE AMENDMENTS SEC. | | | 607.7 . | | | | | | FLOOR DRAINS SHALL BE EQUIPPED W/ TRAP | | | PRIMERS.SPC 409.4.1.4. | | | | | | AN APPROVED BACKFLOW PREVENTER SHALL BE | | | INSTALLED ON THE BYPASS ON THE WATER | | | SERVICE AND ON THE FEED WATER LINE TO | | | THE BOILER PER SPC SEC.606.1,606.3.5. | | | | | | SUBMIT A LEGIBLE COPY OF THE MANUF.SHEET | | | FOR THE GREASE INTERCEPTOR.SPC 1004.2. |
|