Plan Review Notes
Plan Review Notes For Permit 99070843
Permit Number 99070843
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2001-05-02 00:00:001) DUCT SMOKE DETECTORS REQUIRED IN ALL
 AIR HANDLING SYSTEMS OVER 2000 CFM AND
 SERVING MEANS OF EGRESS AREAS. WHEN
 ACTIVATED, THE AIR HANDLING EQUIPMENT
 IS TO SHUT DOWN AND CAUSE THE FIRE
 ALARM SYSTEM TO ACTIVATE.
 2) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 3) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 4) FIRE DAMPERS TO COMPLY WITH UL 555.
 ALL FIRE DAMPERS ARE TO BE DROP TESTED
 AFTER INSTALLATION.
 5) SEATING INSTALLATION SUBJECT TO THE
 APPROVAL OF THE FIRE PREVENTION BUREAU.
 6) DOORS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS SHALL BE EQUIPPED WITH
 PANIC HARDWARE. FIRE DOORS SHALL BE
 EQUIPPED WITH FIRE EXIT PANIC HARDWARE.
 7) PLEASE CONTACT THIS OFFICE TO DISCUSS
 SEATING ARRANGEMENT ON THE MAIN FLOOR
 OF THE BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910