| Plan Review Notes For Permit 99070843 |
| Permit Number |
99070843 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-05-02 00:00:00 | 1) DUCT SMOKE DETECTORS REQUIRED IN ALL | | | AIR HANDLING SYSTEMS OVER 2000 CFM AND | | | SERVING MEANS OF EGRESS AREAS. WHEN | | | ACTIVATED, THE AIR HANDLING EQUIPMENT | | | IS TO SHUT DOWN AND CAUSE THE FIRE | | | ALARM SYSTEM TO ACTIVATE. | | | 2) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 3) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 4) FIRE DAMPERS TO COMPLY WITH UL 555. | | | ALL FIRE DAMPERS ARE TO BE DROP TESTED | | | AFTER INSTALLATION. | | | 5) SEATING INSTALLATION SUBJECT TO THE | | | APPROVAL OF THE FIRE PREVENTION BUREAU. | | | 6) DOORS SUBJECT TO AN OCCUPANCY OF 100 | | | OR MORE PERSONS SHALL BE EQUIPPED WITH | | | PANIC HARDWARE. FIRE DOORS SHALL BE | | | EQUIPPED WITH FIRE EXIT PANIC HARDWARE. | | | 7) PLEASE CONTACT THIS OFFICE TO DISCUSS | | | SEATING ARRANGEMENT ON THE MAIN FLOOR | | | OF THE BUILDING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|