| 2001-02-14 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SUBMIT A RISER SHEET |
| | WITHCORRELATING INFORMATION SHOWING |
| | CLARIFICATION ON LOCATIONS OF |
| | TRANSFORMERS. |
| | WE NEED CLARIFICATION ON HOW FAR AWAY |
| | PANELS/ AND DISCONNECTS ARE. THIS IS |
| | NEEDED FOR SECONDARY(S) OF ALL |
| | TRANSFORMERS IN THE BLDG. ALL MUST MEET |
| | 240-21-C 2&3 |
| | |
| | 2)NOTE: PLEASE NOTE, ON SHEET E902 YOU |
| | ARE SHOWING TWO LOCATIONS WHERE |
| | TRANSFORMERS ARE BEING TAPPED AND GOING |
| | TO GUTTERS AND BEING TAPPED AGAIN, |
| | PLEASE NOTE |
| | THAT THIS VIOLATES 240-21. |
| | |
| | PLEASE NOTE THAT ALL THE REQUIREMENTS |
| | FOR TAPPED CONDUCTORS NEED TO BE MET. |
| | FOR 10` AND 25` |
| | CONDUCTORS FEEDING "LRU" DIST. PANEL |
| | ARERATED FOR LEESTHAN THE 600A RATED |
| | BOARD. |
| | |
| | 3)NOTE: ALSO PLEASE NOTE THAT ALL THE |
| | REQUIREMENTS FOR 110-26 AND 384-7 NEED T |
| | O BE MET. PANELS AND TRANSFORMERS ARE |
| | SHOWN IN STORAGE AND CLEANING CLOSETS. |
| | THIS IS VIOLATES THE ABOVE MENTIONED ART |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS PLEAS |
| | E CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |
| | OR |
| | JAKE LEAHY |
| | CHEIF ELECTRICAL INSPECTOR |
| | 561-659-8096 EXT 8372 |