| 2001-01-08 00:00:00 | NUMBER OF REQUIRED DRINKING FOUNTAINS |
| | SHALL COMPLY W/SPC TABLE 407.(A TOTAL OF |
| | 17 ARE REQD.) |
| | |
| | CLEARLY SHOW THAT FLOORS AND WALLS ARE |
| | NON-ABSORBENT TO A HEIGHT OF 4'PER SBC |
| | SEC.1204.2 |
| | |
| | AN ADDITIONAL HANDICAP STALL COMPLYING |
| | W/FACBC SEC.4.22.4 SHALL BE REQUIRED |
| | IN CORE RESTROOMS OF 6 STALLS OR MORE. |
| | |
| | TOILET ROOMS OTHER THAN THOSE |
| | LOCATED IN PUBLIC AND COMMON USE AREAS |
| | SHALL BE HANDICAPADAPTABLE PER FACBC |
| | SEC.4.1.3(11). |
| | |
| | HANDICAP STALLS LOCATED IN CORE REST- |
| | ROOMS SHALL COMPLY W/FACBC SEC.4.17.3. |
| | (SEE EXCEPTION: NEW CONSTRUCTION). |
| | |
| | DOORS IN HANDICAP TOILET ROOMS AND |
| | STALLS SHALL NOT SWING INTO CLEAR FLOOR |
| | FLOOR SPACE FOR ANY FIXTURE PER FACBC. |
| | |
| | HANDICAP STALL IN MEN'S DRESSING ROOM |
| | SHALL COMPLY W/FACBC SEC.4.17.3 |
| | |
| | CLEARLY SHOW THE DIMENSIONS OF THE |
| | HANDICAP SHOWERS.COMPLY W/FACBC SEC. |
| | 4.21.2. |
| | |
| | SHOW TYPICAL FIXTURE CLEARANCE OF |
| | URINALS ON THE PLANS.SPC SEC.403.4. |
| | |
| | HANDICAP TOILET STALLS AND TOILET ROOMS |
| | SHALL HAVE 60" CLEAR TURNING SPACE PER |
| | FACBC SECTION 4.2.3.(WATER CLOSET |
| | INFRINGES ON TURNING SPACE IN SOME ROOMS |
| | CHECK ALL STALLS AND ROOMS.) |
| | |
| | SEATS IN HANDICAP SHOWERS SHALL COMPLY |
| | W/FACBC SEC.4.21.3(REQD.IN 36"X 36"STALL |
| | |
| | CLEAR FLOOR SPACE UNDER H.C.LAVATORIES |
| | SHALL BE A MIN.OF 29" PER FACBC SEC. |
| | 4.19.2. |
| | |
| | CLEARLY SHOW THE REQD.HEIGHT OF THE H.C. |
| | WATER ON SHT.A204.(17"-19".)PER FACBC |
| | SEC.4.16.3. |
| | |
| | GRAB BARS BEHIND WATER CLOSETS SHALL BE |
| | 36"LONG PER FACBC SEC.4.16.4,4.17.6.(SEE |
| | SHT.A204.) |
| | |
| | SHOWER VALVES SHALL COMPLY W/SPC SEC.613 |
| | NOTE ON PLANS. |
| | |
| | DORMITORY ROOMS SHALL COMPLY W/FEDERAL |
| | FAIR HOUSING ACT. |
| | |
| | SHT.A105 SHOWS A CLEANING/STORAGE AREA |
| | W/WASHER & DRYER.WASHERS ARE ALSO SHOWN |
| | IN THE DORMS.THIS IS A COMMERCIAL |
| | FACILITY AND REQS.AN INTERCEPTOR PER |
| | SPC SEC.1004.1,1004.10.1.1. |
| | AND CLEANING /STORAGE AREA SHALL BE |
| | EQUIPPED W/A FLOOR DRAIN.SPC SEC.409.4.5 |
| | |
| | SHT.A204-SHOWER FLOOR SHALL BE DRAINED |
| | SO THAT NO WASTE WATER FROM ANY SHOWER |
| | HEAD WILL PASS OVER FLOOR AREAS OCCUPIED |
| | BY OTHER BATHERS.SPC SEC.409.8.3. |
| | |
| | CONTACT RODNEY COMPO AT CITY OF W.P.B. |
| | REGIONAL WASTEWATER TREATMENT PLANT FOR |
| | REQS./SIZE OF GREASE TRAP.(561)835-7423 |
| | |
| | THE SUBMITTED GAS DRAWING LACKS THE |
| | NECESSARY INFORMATION TO PERFORM A |
| | PROPER REVIEW.SHOW TYPE OF MATERIAL FOR |
| | PIPING,DISTANCE TO MOST REMOTE OUTLET, |
| | CUT SECTIONS OF PIPE,ETC.COMPLY W/STD. |
| | GAS CODE SEC.302,305.2,305.3.2,306,ETC. |
| | INDICATE TYPE OF GAS-NATURAL OR LP. |
| | |
| | SHT.A211-CLEARLY SHOW TERMINATION PT.OF |
| | TRUCK WELL DRAIN.SPC 104.2.1. |
| | |
| | SUBMIT MANUF. SHEETS FOR GAS EQUIP.PER |
| | STD.GAS CODE SEC.402.1 |
| | |
| | THE SUBMITTED SANITARY RISER HAS TOO |
| | MANY CODE VIOLATIONS TO LIST.SUBMIT A |
| | SANITARY RISER THAT COMPLIES W/THE STD. |
| | PLBG.CODE. |
| | |
| | THE SANITARY ISOMETRIC DOESN'T CORRELATE |
| | W/THE BUILDING FLOOR PLAN.SPC 104.2.1. |