Plan Review Notes
Plan Review Notes For Permit 99070843
Permit Number 99070843
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-02-08 00:00:001) NEW BRICK PAVERS ON EXISTING CONCRETE
 STEPS ARE TO BE SLIP RESISTANT.
 2) PLEASE DEFINE BABY ROOM 1617. WHAT
 WILL IT BE USED FOR.
 3) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 4) ALL EXIT DOORS IN THE REQUIRED MEANS
 OF EGRESS SUBJECT TO AN OCCUPANCY OF
 100 OR MORE PERSONS SHALL BE EQUIPPED
 WITH PANIC HARDWARE.
 5) SUFFICIENT EMERGENCY LIGHTING AND
 ILLUMINATED EXIT SIGNS ARE TO BE PRESENT
 WITHIN THE BUILDING.
 6) PLEASE PROVIDE MORE DETAILS ON
 FIXED SEATING PLANNED FOR THE GROUND
 FLOOR.
 7) DUCT SMOKE DETECTION REQUIRED IN ALL
 AIR HANDLING SYSTEMS.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910