| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD PER STD.PLBG.CODE |
| | SEC.407.1.1, 407.1.3 TO ENSURE |
| | COMPLIANCE FOR MINIMUM FIXTURE REQ'S. |
| | FIXTURE REQ'S.SHALL BE BASED ON EQUAL |
| | NUMBER OF MALES AND FEMALES. |
| | |
| | FIXTURE REQ'S.SHALL COMPLY W/FLA.STATUTE |
| | 553.141.(POTTY PARITY.). |
| | |
| | HANDICAP DRINKING FOUNTAINS SHALL COMPLY |
| | W/F.A.C.B.C.SEC.4.1.3(10)(A)(B). |
| | |
| | HANDICAP TOILET STALLS IN DRESSING ROOMS |
| | AND COMMON RESTROOMS SHALL COMPLY W/FLA. |
| | ACCESS.CODE SECS.4.17.3(SEE EXCEPTION: |
| | NEW CONSTTRUCTION.) |
| | |
| | HANDICAP TOILET/STALLS SHALL HAVE 60" |
| | CLEAR TURNING SPACE PER F.A.C.B.C. SEC. |
| | 4.2.3.(WATER CLOSET INFRINGES ON TURNING |
| | SPACE IN SOME ROMMS -CHECK ALL STALLS |
| | AND TOILET ROOMS AND REVISE). |
| | |
| | SEATS IN HANDICAP SHOWERS SHALL COMPLY |
| | W/F.A.C.B.C. SEC.4.21.3. |
| | |
| | CLEARLY SHOW ALL DIMENSIONS OF HANDICAP |
| | SHOWER STALLS.COMPLY W/F.A.C.B.C.SEC. |
| | 4.21.2. |
| | |
| | EACH PUBLIC OR COMMON USE TOILET |
| | FACILITY SHALL COMPLY W/F.A.C.B.C. SEC. |
| | 4.22.(SEE SEC.4.1.2.(6). |
| | |
| | CLEAR FLOOR SPACE UNDER H.C.LAVS.SHALL |
| | COMPLY W/F.A.C.B.C.SEC.4.19.2. |
| | |
| | HEIGHT OF H.C.WATER CLOSETS SHALL COMPLY |
| | W/F.A.C.B.C.SEC.4.16.3. |
| | |
| | AN ADDITIONAL H.C STALL IS REQ'D.IN THE |
| | RESTROOMS PER F.A.C.B.C.SEC.4.22.4 |
| | |
| | DORMITORY ROOMS SHALL COMPLY W/FLA. |
| | ACESS.CODE SEC.9.1 THRU 9.1.5, 9.2.1 - |
| | 9.2. |
| | |
| | GANG SHOWERS SHALL COMPLY W/STD. PLBG. |
| | CODE SEC.409.8.3. |
| | |
| | SHOWER VALVES SHALL COMPLY W/STD.PLBG. |
| | CODE SEC.613.1.(NOTE ON PLANS.). |
| | |
| | SHOW TYPICAL SPACING FOR URINALS PER |
| | STD.PLBG.CODE SEC.403.4. |
| | |
| | HANDICAP SHOWERS SHALL BE EQUIPPED W/ |
| | SPRAY UNITS PER F.A.C.B.C.SEC.4.21.6. |
| | |
| | LINT INTERCEPTORS ARE REQ'D.FOR THE |
| | COMMON LAUNDRY AREAS PER STD.PLBG.CODE |
| | SEC.1004.1,1004.10.1.1. |
| | |
| | LAUNDRY ROOMS SHALL BE EQUIPPED W/FLOOR |
| | DRAINS PER STD.PLBG.CODE SEC.409.4.5. |
| | |
| | SUBMIT A COMPLETE GAS RISER DIAGRAM |
| | SHOWING TYPE OF MATERIAL,APPLIANCES,BTU |
| | LOAD OF EA.APPLIANCE,TOTAL BTU LOAD OF |
| | THE SYSTEM,ETC.COMPLY W/STANDARD GAS |
| | CODE SECS.302, 305.2,305.3.2,306,ETC. |
| | |
| | SUBMIT A WATER AND SANITARY ISOMETRIC |
| | THAT CLEARLY REFLECTS THE ENTIRE SCOPE |
| | OF PLUMBING WORK TO BE PERFORMED.SPC |
| | SEC 104.2.1.(INCLUDE ALL INDIRECT WASTE) |
| | |
| | SPACING OF CLEANOUTS IN THE DRAINAGE |
| | SYSTEM SHALL COMPLY W/SPC SEC.710.2.1 |
| | THRU SEC.712.2. |
| | |
| | FLOOR DRAINS SHALL NOT EXCEED ALLOWABLE |
| | DISTANCES FROM VENT PER TABLE 908.1 OF |
| | SPC. |
| | |
| | SHT.P-5-SHOWS FLOOR DRAIN IN STORAGE |
| | ROOM.DETAIL TYPE OF MATERIALS TO BE |
| | STORED IN THIS ROOM. |
| | |
| | SHT.A 206-SHOWS DRAIN IN TRUCKWELL AREA. |
| | INDICATE TERMINATION PT.OF DRAIN. |
| | |
| | LOCATION OF GREASE INTERCEPTORS SHALL |
| | COMPLY W/STD.PLBG.CODE SEC.1004.8 AND |
| | STATE OF FLA.DEPT.OF HEALTH REQ'S. |
| | |
| | SUBMIT DETAIL OF GREASE INTERCEPTOR FOR |
| | REVIEW.SPC 104.2.1. |
| | --PLANS SHALL BE ROUTED TO PALM BEACH |
| | COUNTY HEALTH UNIT.(561)355-3018. |