Plan Review Notes
Plan Review Notes For Permit 99070843
Permit Number 99070843
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD PER STD.PLBG.CODE
 SEC.407.1.1, 407.1.3 TO ENSURE
 COMPLIANCE FOR MINIMUM FIXTURE REQ'S.
 FIXTURE REQ'S.SHALL BE BASED ON EQUAL
 NUMBER OF MALES AND FEMALES.
  
 FIXTURE REQ'S.SHALL COMPLY W/FLA.STATUTE
 553.141.(POTTY PARITY.).
  
 HANDICAP DRINKING FOUNTAINS SHALL COMPLY
 W/F.A.C.B.C.SEC.4.1.3(10)(A)(B).
  
 HANDICAP TOILET STALLS IN DRESSING ROOMS
 AND COMMON RESTROOMS SHALL COMPLY W/FLA.
 ACCESS.CODE SECS.4.17.3(SEE EXCEPTION:
 NEW CONSTTRUCTION.)
  
 HANDICAP TOILET/STALLS SHALL HAVE 60"
 CLEAR TURNING SPACE PER F.A.C.B.C. SEC.
 4.2.3.(WATER CLOSET INFRINGES ON TURNING
 SPACE IN SOME ROMMS -CHECK ALL STALLS
 AND TOILET ROOMS AND REVISE).
  
 SEATS IN HANDICAP SHOWERS SHALL COMPLY
 W/F.A.C.B.C. SEC.4.21.3.
  
 CLEARLY SHOW ALL DIMENSIONS OF HANDICAP
 SHOWER STALLS.COMPLY W/F.A.C.B.C.SEC.
 4.21.2.
  
 EACH PUBLIC OR COMMON USE TOILET
 FACILITY SHALL COMPLY W/F.A.C.B.C. SEC.
 4.22.(SEE SEC.4.1.2.(6).
  
 CLEAR FLOOR SPACE UNDER H.C.LAVS.SHALL
 COMPLY W/F.A.C.B.C.SEC.4.19.2.
  
 HEIGHT OF H.C.WATER CLOSETS SHALL COMPLY
 W/F.A.C.B.C.SEC.4.16.3.
  
 AN ADDITIONAL H.C STALL IS REQ'D.IN THE
 RESTROOMS PER F.A.C.B.C.SEC.4.22.4
  
 DORMITORY ROOMS SHALL COMPLY W/FLA.
 ACESS.CODE SEC.9.1 THRU 9.1.5, 9.2.1 -
 9.2.
  
 GANG SHOWERS SHALL COMPLY W/STD. PLBG.
 CODE SEC.409.8.3.
  
 SHOWER VALVES SHALL COMPLY W/STD.PLBG.
 CODE SEC.613.1.(NOTE ON PLANS.).
  
 SHOW TYPICAL SPACING FOR URINALS PER
 STD.PLBG.CODE SEC.403.4.
  
 HANDICAP SHOWERS SHALL BE EQUIPPED W/
 SPRAY UNITS PER F.A.C.B.C.SEC.4.21.6.
  
 LINT INTERCEPTORS ARE REQ'D.FOR THE
 COMMON LAUNDRY AREAS PER STD.PLBG.CODE
 SEC.1004.1,1004.10.1.1.
  
 LAUNDRY ROOMS SHALL BE EQUIPPED W/FLOOR
 DRAINS PER STD.PLBG.CODE SEC.409.4.5.
  
 SUBMIT A COMPLETE GAS RISER DIAGRAM
 SHOWING TYPE OF MATERIAL,APPLIANCES,BTU
 LOAD OF EA.APPLIANCE,TOTAL BTU LOAD OF
 THE SYSTEM,ETC.COMPLY W/STANDARD GAS
 CODE SECS.302, 305.2,305.3.2,306,ETC.
  
 SUBMIT A WATER AND SANITARY ISOMETRIC
 THAT CLEARLY REFLECTS THE ENTIRE SCOPE
 OF PLUMBING WORK TO BE PERFORMED.SPC
 SEC 104.2.1.(INCLUDE ALL INDIRECT WASTE)
  
 SPACING OF CLEANOUTS IN THE DRAINAGE
 SYSTEM SHALL COMPLY W/SPC SEC.710.2.1
 THRU SEC.712.2.
  
 FLOOR DRAINS SHALL NOT EXCEED ALLOWABLE
 DISTANCES FROM VENT PER TABLE 908.1 OF
 SPC.
  
 SHT.P-5-SHOWS FLOOR DRAIN IN STORAGE
 ROOM.DETAIL TYPE OF MATERIALS TO BE
 STORED IN THIS ROOM.
  
 SHT.A 206-SHOWS DRAIN IN TRUCKWELL AREA.
 INDICATE TERMINATION PT.OF DRAIN.
  
 LOCATION OF GREASE INTERCEPTORS SHALL
 COMPLY W/STD.PLBG.CODE SEC.1004.8 AND
 STATE OF FLA.DEPT.OF HEALTH REQ'S.
  
 SUBMIT DETAIL OF GREASE INTERCEPTOR FOR
 REVIEW.SPC 104.2.1.
 --PLANS SHALL BE ROUTED TO PALM BEACH
 COUNTY HEALTH UNIT.(561)355-3018.