2001-01-08 00:00:00************CORRECTED*******************
  
 1) AIR BALANCE SCHEDULE INDICATES RETURN
 AIR CFM = SUPPLY AIR CFM, THAT LEAVES NO
 ROOM FOR REQUIRED CFM OF OUTSIDE AIR FOR
 AHU 1-4
 2) LINE 44 SHOWS EXHAUST OUTLET WITHIN
 10' OF OUTSIDE AIR INTAKE
 3) KITCHEN HOOD AND EXHAUST TO COMPLY W/
 1997 SMC 504 AND NFPA 96 SEPARATE PERMIT
 AND PLANS TO BE SUBMITTED WITH PERMIT AP
 4) MEN'S AND WOMEN'S TOILET ROOMS DO NOT
 SHOW BALANCE BETWEEN EXHAUST AIR AND
 SUPPLY AIR PER 1997 SMC 501.2
 5) STORAGE ROOMS TO BE VENTILATED PER
 1997 SMC 403
 6)NO OUTSIDE AIR FOR BATHROOMS PER
 ASHRAE 62-89
 7) ROOMS WITH GREATER THAN 300CFM SUPPLY
 AIR TO HAVE RETURN FROM AREA PER SMC 501
 .2
 8) EXHAUST FAN TERMINATION FOR EF#7 SHAL
 NOT BE WITHIN 10' OF OUTSIDE AIR INTAKE
 FOR FC-1F PER SMC 506.1
 9) FC-1T SHOWS EQUAL SUPPLY AIR AND
 RETURN TO UNIT, WHERE IS OUTSIDE AIR
 BALANCE IN CALCULATIONS
 10)WHAT UNIT SUPPLYS OFFICES BETWEEN
 LINE 21 AND 23 ON M-5 (FC-1H)?
 11) EXHAUST FAN IN TOILET RM BY LINE 14
 NOT LABELED OFFICE BY SAME LINE NOT VENT
 ILATED
 12) BOILER ROOM NOT VENTILATED
 13) NO COMBUSTION AIR SHOWN FOR BOILER,
 SHOW CACULATIONS ON REQUIRED AMOUNT
 14) NO INFORMATION ON DRYER VENTING
 15) SHOW OUTSIDE AIR TO EXISTING FCU IN
 MECH RM
 16) NO VENTILATION SHOWN FOR SWITCHGEAR
 ROOM
 17) LINE 5 SHOWS OUTSIDE AIR INTAKE LOUV
 ER WITHIN 10' OF EXHAUST AIR LOUVER
 18) BALANCE BETWEEN EXHAUST AIR AND
 SUPPLY AIR AND OUTSIDE AIR NOT PER SMC
 501.2
 19) WHERE DO EXHAUST FANS #8'S AND #10'S
 TERMINATE? (M-6)
 20) HALL ROOF EXHAUST SHOWN ON M-1 AIR
 BALANCE ARE NOT SHOWN ON PLANS OR EF
 SCHEDULE. WHERE DO THEY TERMINATE.
 PROVIDE AIR BALANCE SCHEDULE TO COMPLY
 WITH SMC 501.2
 21)ALL DUCTS PENETRATING RATED WALLS TO
 HAVE FIRE DAMPERS PER SMC 610 SHOW ON
 PLAN
 22) NO INFORMATION SHOWN ON FAN SHUT
 DOWN BY DUCT SMOKE DETECTORS. SHOW COMP-
 LIANCE WITH SMC 406 AND NFPA 90A 4-4.4.2
 23) AHU RMS TO BE VENTILATED PER SMC 403
  
 NOTE: PRELIMINARY REVIEW. INSUFFICIENT
 IFORMATION TO DETERMINE CODE COMPLIANCE
 AS PRESENTED