2001-01-08 00:00:001)NEED LOAD CALCULATIONS ON PANELS TO
 REFLECT CONTIN LDS,MOST OF THE
 PANELS SHOW 4 TO 8 AMPERES FOR THE
 LIGHTING IN EACH PANEL.THIS CAN,T
 BE CORRECT WHEN THERE IS LARGE
 LIGHTING LOADS IN THESE PANELS
  
 2)PANEL LPL-8SHOW 8.32 AMPS FOR THE
 CONTINUOUS LOAD FACTOR WHEN THERE
 IS 15,600VA WORTH OF LOAD3900
 VA CONTINUOUS LOAD CONTRIBUTION
 COMES OUT AT 16.25 AMPSPLEASE
 CHECK ALL PANEL SCHEDULES FOR THE
 CORRECT LOADS!
  
 3)NEW MAIN 3000 AMPERES SHOW LOAD
 CALCULATION FOR THIS SWITCH.
  
 4)AT NEWTRANSFER SWITCH YOU NEED A
 DISCONNECT FOR THE LINE SIDE OF THE
 EMERGENCY FEED AT TRANSFER SWITCH!!
  
 5)NOTE #5 WAS LISTED ON THE ORIGINAL
 CHECK LIST!YOUR RISER DOES NOT
 REFLECT THIS 225-8, 230-72
  
 6)THE CITY NEEDS A ONE LINE DIAGRAM
 FOR THE RISER THAT WILL BE USED
 SHOW WHAT THE FINISHED RISER WILL
 LOOK LIKE.
  
 7)ACCORDING TO THE PLANS YOU SHOW AN
 EXISTING RISER WITH THE NOTE TO BE
 REMOVED UNLESS NOTED,DPP1 SHOULD BE
 REMOVED BUT SHOWS UP ON NEW RISER
 PLEASE FIXSEE NOTE #6