| 2001-01-08 00:00:00 | 1)NEED LOAD CALCULATIONS ON PANELS TO |
| | REFLECT CONTIN LDS,MOST OF THE |
| | PANELS SHOW 4 TO 8 AMPERES FOR THE |
| | LIGHTING IN EACH PANEL.THIS CAN,T |
| | BE CORRECT WHEN THERE IS LARGE |
| | LIGHTING LOADS IN THESE PANELS |
| | |
| | 2)PANEL LPL-8SHOW 8.32 AMPS FOR THE |
| | CONTINUOUS LOAD FACTOR WHEN THERE |
| | IS 15,600VA WORTH OF LOAD3900 |
| | VA CONTINUOUS LOAD CONTRIBUTION |
| | COMES OUT AT 16.25 AMPSPLEASE |
| | CHECK ALL PANEL SCHEDULES FOR THE |
| | CORRECT LOADS! |
| | |
| | 3)NEW MAIN 3000 AMPERES SHOW LOAD |
| | CALCULATION FOR THIS SWITCH. |
| | |
| | 4)AT NEWTRANSFER SWITCH YOU NEED A |
| | DISCONNECT FOR THE LINE SIDE OF THE |
| | EMERGENCY FEED AT TRANSFER SWITCH!! |
| | |
| | 5)NOTE #5 WAS LISTED ON THE ORIGINAL |
| | CHECK LIST!YOUR RISER DOES NOT |
| | REFLECT THIS 225-8, 230-72 |
| | |
| | 6)THE CITY NEEDS A ONE LINE DIAGRAM |
| | FOR THE RISER THAT WILL BE USED |
| | SHOW WHAT THE FINISHED RISER WILL |
| | LOOK LIKE. |
| | |
| | 7)ACCORDING TO THE PLANS YOU SHOW AN |
| | EXISTING RISER WITH THE NOTE TO BE |
| | REMOVED UNLESS NOTED,DPP1 SHOULD BE |
| | REMOVED BUT SHOWS UP ON NEW RISER |
| | PLEASE FIXSEE NOTE #6 |