Plan Review Notes
Plan Review Notes For Permit 99070655
Permit Number 99070655
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00 
  
  
  
  
  
  
  
  
  
 SUBMIT DETAIL FOR WATER AND SANITARY
 CONNECTIONS TO X-RAY PROCESSOR.(IF
 APPLICABLE.SEE ABOVE COMMENT.)SPC 104.2.
  
 BREAKROOM SINK SHALL COMPLY W/F.A.C.B.C.
 SECS.4.24.1.-4.24.7.
 0 /
 SHT.A-3-CLEARANCE TO BOTTOM OF LAV.FROM
 F.F.SHALL COMPLY W/F.A.C.B.C.SEC.4.19.2
  
 HANDICAP DRINKING FOUNTAIN SHALL COMPLY
 W/F.A.C.B.C. SEC.4.1.3 (10)(A).
  
 SHT.P-2 - RELIEF LINE AND PAN DRAIN
 SHALL NOT BE INTERCONNECTED PER SPC
 SEC.507.8.3.,507.8.4.
  
 SUBMIT A COMPLETE WATER ISOMETRIC THAT
 REFLECTS ENTIRE SCOPE OF WORK TO BE
 PERFORMED.WATER SUPPLY CONTROL SHALL
 COMPLY W/SPC 610.4.1, 610.4.2.
  
 SIZE ALL SECTIONS OF THE SANITARY RISER
 AND NOTE SLOPE OF PIPE PER SPC SEC.714.1
 714.2.
  
 INDICATE OCCUPANT LOAD ON PLANS TO
 ENSURE COMPLIANCE W/ SPC TABLE 407.