| Plan Review Notes For Permit 99070649 |
| Permit Number |
99070649 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CLEARLY SHOW THAT WALLS AND FLOORS OF | | | TOILET ROOMS COMPLY W/STD.BLDG.CODE SEC. | | | 1204.2. | | | | | | EFFLUENT FROM PROCESSOR SHALL BE | | | RENDERED INNOCUOUS PRIOR TO DISCHARGE TO | | | SANITARY SEWER.SUBMIT VERIFICATION FROM | | | MANUFACTURER OF PH RANGE.(ACCEPTABLE | | | RANGE IS BETWEEN 5-10.)SPC 801.4. | | | | | | SHT.A-3.CLEARANCE TO BOTTOM OF LAV.FROM | | | F.F.SHALL COMPLY W/F.A.C.B.C.SEC.4.19.2. | | | | | | HANDICAP DRINKING FOUNTAIN SHALL COMPLY | | | W/F.A.C.B.C.SEC.4.1.3(10)(A). | | | | | | THE MINIMUM FIXTURE REQS.FOR THE | | | OCCUPANT LOAD SHALL COMPLY W/TABLE 407 | | | OF SPC. | | | | | | CLEARLY SIZE ALL VENTS ON THE SANITARY | | | SYSTEM.COMPLY W/TABLES 920.2,920.4 OF | | | SPC. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | 610.4.1 ,610.4.2. | | | | | | OVER 4 FIXTURES ARE CONNECTED TO 1/2" | | | H.W.PER COUNTYWIDE AMENDMENTS SEC.607.7 | | | | | | SHT.A-4.BREAKROOM SINK SHALL COMPLY W/ | | | F.A.C.B.C.SEC.4.24.1 -4.24.7. |
|