| Plan Review Notes For Permit 99070232 |
| Permit Number |
99070232 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1-RISER DIAGRAM SHOWS 150 AMP MAIN AND | | | PANEL AND LOAD CALCULATION SHOWS | | | 182 AMPS?????? | | | | | | 2-PLEASE CHANGE PANEL SIZE AND THE | | | WIRE THAT GOES TO THIS PANEL!!! |
|