| Plan Review Notes For Permit 99070145 |
| Permit Number |
99070145 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************** | | | | | | 1)NOTE:REQ`MENTS FOR KITCHEN PENINSULAR | | | AS PER ART;210-52-C-3 | | | 2)NOTE:ART 210-52E REQ`S RECEPTS.FRONT | | | AND BACK OF DWELLING UNIT. | | | 3)NOTE:ART 210-52-C-1 KITCHENCOUNTER | | | SPACE REQ`S RECEPT.12" OF SPACE. | | | 4)NOTE:ART;210-63 REQ`S RECEPT.FOR A/C | | | COND.UNIT. | | | 5(NFPA-72 REQ`S SMOKE DETECTORS INSIDE | | | AND OUTSIDE BEDROOMS. | | | 6)NOTE:BEDROOM #3 2` OF WALL SPACE AS | | | PER ART.210-52 | | | 7)NOTE:NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT ARTS.215-5/110-9 | | | | | | PLEASE HAVE SUBMITTED AND APPROVED | | | BEFORE ROUGH ELECTRICAL INSPECTION. |
|