| Plan Review Notes For Permit 99070088 |
| Permit Number |
99070088 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | | | | NOTE: 210-70 SWITCH AND LIGHT REQ`D AT | | | MEANS OF EGRESS. | | | NOTE:210-52C REQ`D RECEPTS. SERVING | | | KITCHEN COUNTER SPACE. | | | NOTE:210-8-A-6 ALL RECEPTS. SERVING KIT- | | | -CHEN COUNTER SPACE ARE TO BE GFI/GFI | | | PROTECTED. | | | NOTE:210-63 WP GFI RECEPT. REQ`D FOR A/C | | | EQUIP. | | | NOTE:210-52A MISSING RECEPTS.AS PER | | | 2`6`12`RULE. | | | NOTE:NFPA-72 SMOKE DETECTORS REQ`D | | | INSIDE AND OUTSIDE BEDROOMS. | | | NOTE:SHOW COMPLETE RISER DIAGRAM TO | | | INCLUDE METER,PANEL,DISC, WIRE SIZE, | | | CONDUIT SIZES.GRPOUNDING ELECTRODE | | | SYSTEM.GRND.ROD,CWP,ETC. | | | NOTE:440-11 A/C DISC. REQ`D | | | | | | NEED THE ABOVE INFORMATION RESUBMITTED | | | AND APPROVED BEFORE ROUGH INSPECTION. | | | | | | NOTE:410-8 LIGHTING CLEARANCES REQ`D | | | FOR CLOSETS AND THE TYPE OF FIXTURES | | | PERMITTED. |
|