Plan Review Notes
Plan Review Notes For Permit 99070088
Permit Number 99070088
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************PROVISO******************
  
 NOTE: 210-70 SWITCH AND LIGHT REQ`D AT
 MEANS OF EGRESS.
 NOTE:210-52C REQ`D RECEPTS. SERVING
 KITCHEN COUNTER SPACE.
 NOTE:210-8-A-6 ALL RECEPTS. SERVING KIT-
 -CHEN COUNTER SPACE ARE TO BE GFI/GFI
 PROTECTED.
 NOTE:210-63 WP GFI RECEPT. REQ`D FOR A/C
 EQUIP.
 NOTE:210-52A MISSING RECEPTS.AS PER
 2`6`12`RULE.
 NOTE:NFPA-72 SMOKE DETECTORS REQ`D
 INSIDE AND OUTSIDE BEDROOMS.
 NOTE:SHOW COMPLETE RISER DIAGRAM TO
 INCLUDE METER,PANEL,DISC, WIRE SIZE,
 CONDUIT SIZES.GRPOUNDING ELECTRODE
 SYSTEM.GRND.ROD,CWP,ETC.
 NOTE:440-11 A/C DISC. REQ`D
  
 NEED THE ABOVE INFORMATION RESUBMITTED
 AND APPROVED BEFORE ROUGH INSPECTION.
  
 NOTE:410-8 LIGHTING CLEARANCES REQ`D
 FOR CLOSETS AND THE TYPE OF FIXTURES
 PERMITTED.