| 2001-01-08 00:00:00 | *************PROVISO******************* |
| | |
| | 1) DRYER VENT DUCTS TO RUN TO OUTSIDE OF |
| | THE BUILDING. 1994 SMC 509.1 (1) DUCTS |
| | SHALL NOT BE CONNECTED TO A VENT |
| | CONNECTOR, GAS VENT, CHIMNEY, CRAWL |
| | SPACE OR OTHER SIMILIAR CONCEALED SPACE. |
| | THE EXCEPTION 1994 SMC 610.1.3(2) WHERE |
| | BRANCH DUCTS CONNECT TO RETURN RISERS |
| | IN WHICH THE AIR IS UPWARD AND SUBDUCTS |
| | AT LEAST 22 INCHES LONG ARE CARRIED UP |
| | INSIDE THE RISER AT EACH INLET.,DOES NOT |
| | APPLY TO DRYER VENTS |
| | 2) THE EXHAUST FAN FOR THE DRYER VENT |
| | CHASE DOES NOT COMPLY WITH THE REQUIR- |
| | MENTS OF 1994 SMC 509.3 THE WALL OR ROOF |
| | CAP SHALL BE NONSCREENED WITH BACKDRAFT |
| | DAMPER. |
| | 3)OVERFLOW PROTECTION REQUIRED ON AHU'S |
| | 4) EXHAUST FROM GENERATOR TO TERMINATE |
| | MIN. 10 FT FROM PARKING AREAS, WINDOWS, |
| | DOOR OR AIR INTAKE OPENINGS AND AT LEAST |
| | 10 FT. ABOVE ADJOINING ABOVE ADJOINING |
| | GRADE LEVEL, PER 1994 SMC 506.1 |
| | 5) 1994 SMC 406.2 REQUIRES SYSTEMS SERV- |
| | ING AREAS USED FOR EGRESS TO HAVE AUTO- |
| | MATIC FAN SHUT DOWN. PROVIDE AUTOMATIC |
| | FAN SHUT DOWN FOR AHU 4. |
| | 6)1994 SMC 406.5 SPECIAL PROVISIONS FOR |
| | HIGH RISE GROUP R BLDGS REQUIRES A SMOKE |
| | DETECTOR INSTALLED IN THE DUCT AT EACH |
| | CONNECTION TO A VERTICAL DUCT OR RISER |
| | SERVING A RECIRCULATING AIR SYSTEM OF |
| | MORE THAN ONE STORY. PROVIDE DETAIL OF |
| | LOCATON AND TYPE DETECTOR.1994SBC412.2.1 |
| | 7)PROVIDE INFORMATION ON SMOKE CONTROL |
| | SHOWING COMPLIANCE WITH 1994 SBC 412.5 |