| Plan Review Notes For Permit 99061599 |
| Permit Number |
99061599 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | INDICATE TYPE OF PIPING TO BE INSTALLED | | | FOR GAS INSTALLATION.COMPLY W/STD.GAS | | | ODE SEC.306.(CLARIFY SCH."D"PIPING) | | | | | | GAS PIPING SHALL NOT BE INSTALLED UNDER | | | BUILDING OR FLOOR SLAB PER STD.GAS CODE | | | SEC.308.3.1,308.4.1. | | | | | | INDICATE GAS SUPPLY PRESSURE ON PLANS | | | FOR PROPER SIZING.STD.GAS CODE SEC.305.2 | | | 305.4. | | | | | | SUBMIT EXISTING TOTAL BTU LOAD ON THE | | | GAS SYSTEM TO ENSURE PROPER SIZING AND | | | TOTAL DEVELOPED LENGTH OF EXISTING | | | SYSTEM.STD.GAS CODE SEC.302. | | | | | | SUBMIT MANUF.SHEETS FOR HIBACHI TABLES. | | | APPLIANCES SHALL BE LISTED PER STD.GAS | | | CODE SEC.402.1. |
|