Plan Review Notes
Plan Review Notes For Permit 99061417
Permit Number 99061417
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00CURBS IN HANDICAP SHOWERS SHALL BE MAX.
 1/2" PER FACBC SEC.4.21.7.
  
 SHT.8.3-CLEAR FLOOR SPACE UNDER HANDICAP
 LAV.SHALL BE MIN.29" PER FACBC SEC.
 4.19.2.
  
 CIRCUIT AND LOOP VENTING SYSTEM FOR THE
 SANITARY SYSTEM SHALL COMPLY W/SPC SEC.
 914.1.(A RELIEF VENT,STACK VENT OR VENT
 STACK IS REQD.DOWNSTREAM OF FIRST HORIZ.
 FIXTURE CONNECTION.SPC SEC.914.1.
  
 A DRINKING FOUNTAIN IS REQD.ON THE 2ND
 FLOOR PER SPC TABLE 407 AND MUST COMPLY
 W/FACBC SEC.4.1.3.(10)(A),4.15.