| Plan Review Notes For Permit 99061417 |
| Permit Number |
99061417 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CURBS IN HANDICAP SHOWERS SHALL BE MAX. | | | 1/2" PER FACBC SEC.4.21.7. | | | | | | SHT.8.3-CLEAR FLOOR SPACE UNDER HANDICAP | | | LAV.SHALL BE MIN.29" PER FACBC SEC. | | | 4.19.2. | | | | | | CIRCUIT AND LOOP VENTING SYSTEM FOR THE | | | SANITARY SYSTEM SHALL COMPLY W/SPC SEC. | | | 914.1.(A RELIEF VENT,STACK VENT OR VENT | | | STACK IS REQD.DOWNSTREAM OF FIRST HORIZ. | | | FIXTURE CONNECTION.SPC SEC.914.1. | | | | | | A DRINKING FOUNTAIN IS REQD.ON THE 2ND | | | FLOOR PER SPC TABLE 407 AND MUST COMPLY | | | W/FACBC SEC.4.1.3.(10)(A),4.15. |
|