| Date |
Text |
| 2001-01-08 00:00:00 | WOMEN'S RESTROOM-THE ACCESIBLE WATER |
| | CLOSET SHALL BE LOCATED IN THE CORNER, |
| | DIAGONAL TO DOOR.F.A.C.B.C.SEC.4.17.3. |
| | |
| | SINKS IN LOUNGE/BREAKROOM SHALL COMPLY |
| | W/F.A.C.B.C.SEC.4.1.1(A),4.24.1-4.24.7. |
| | (THESE AREAS ARE NOT CLASSED AS WORK |
| | AREAS.) |
| | |
| | SHT.8.3-CLEAR FLOOR SPACE UNDER H.C.LAV. |
| | SHALL COMPLY W/F.A.C.B.C.SEC.4.19.2. |
| | |
| | SIZE OF SHOWER STALLS SHALL COMPLY W/ |
| | F.A.C.B.C. SEC.4.21.2-4.21.8 & FIGURES |
| | 35(A)(B). |
| | |
| | H.C.DRINKING FOUNTAIN SHALL COMPLY W/ |
| | F.A.C.B.C.SEC.4.1.3(10)(A). |
| | |
| | SUBMIT OCCUPANT LOAD FOR MINIMUM FIXTURE |
| | REQ'S.PER STD.PLBG.CODE TABLE 407. |
| | |
| | INDICATE SLOPE OF SANITARY SYSTEM ON |
| | PLAN PER STD.PLBG.CODE SEC.705.2,705.3. |
| | |
| | CIRCUIT AND LOOP SYSTEM SHALL COMPY |
| | W/STD.PLBG.CODE SEC.914.1-914.3.4. |
| | |
| | WATER TO APPLIANCES SHALL BE PROTECTED |
| | AGAINST BACKFLOW PER STD.PLBG.CODE SEC. |
| | 606. |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/ |
| | STD.PLBG.CODE SEC.610.4.1,610.4.2. |
| | |
| | WATER PURIFICATION SYSTEM SHALL BE NSF |
| | APPROVED PER STD.PLBG.CODE SEC.615.1. |
| | |
| | MAX.OF 2 FIXTURES SHALL BE SUPPLIED BY |
| | 1/2" C.W.& 4 FIXTURES BY 1/2"H.W.PER |
| | COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE. |