| Plan Review Notes For Permit 99061321 |
| Permit Number |
99061321 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************PROVISO**************** | | | | | | NOTE:SUBMIT PLANS WITH AIC RATING FIG. | | | FROM FAULT CURRENT CALCULATIONS DRAW ON | | | PANEL SCHED/RISER DIAGRAM.ART215-5 | | | NOTE:PLANS SHOW GARAGE DOOR OPENER BUT | | | G.D.O. IS NOT ON PANEL SCHED. AND IS NOT | | | FIGUREDIN THE LOAD CACULATIONS. | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | | | | PLEASE RESUBMIT THE ABOVE INFORMATION | | | BEFORE ROUGH INSPECTION IS CALLED IN. |
|