| Plan Review Notes For Permit 99061284 |
| Permit Number |
99061284 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT A WATER RISER DIAGRAM FOR REVIEW. | | | SPC SEC.104.2.1, | | | | | | CLEARLY SHOW ON PLAN WHERE AND HOW | | | EFFLUENT FROM EMERG.EYEWASH WILL BE | | | DISPOSED.SPC 301.4, 301.11.1,& 301.11 | | | (DRAINAGE TO FLOOR W/O FLOOR DRAIN WILL | | | CREATE A HAZARD. | | | NOTE:PVC CANNOT BE USED FOR WATER DIST. | | | PER SPC 611.2,611.3. |
|