Plan Review Notes
Plan Review Notes For Permit 99061270
Permit Number 99061270
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO******************
  
 NEED TO SUBMIT AIC RATING FROM FAULT
 CURRENT CALCULATIONS.PLEASE SHOW ON
 PLANS ON PANEL SCHED.215-5
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:EQUIPMENT GROUNDING CONDUCTOR
 REQ`D FROM MAIN DISCONNECT TO PANEL.
 ART'S.250-92/250-95
  
 PLEASE RESUBMIT BEFORE ROUGH INSPECTION
 IS CALLED IN.