| Plan Review Notes For Permit 99061218 |
| Permit Number |
99061218 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO***************** | | | 1) DENTAL VACUUM AND COMPRESSED AIR TO | | | BE INSTALLED AND TESTED UNDER 1996 NFPA | | | 99C | | | 2) MECHANICAL PERMIT REQUIRED FOR INSTAL | | | LATION OF ABOVE SYSTEM. PROVIDE DETAILED | | | PLANS SHOWING COMPLIANCE WITH NFPA 99C | | | I.E 4-5.2.2.3 REQUIRES ACCESSIBLE CLEAN- | | | OUTS FOR VACUUM PIPING AND 4-5.1.1.3(E,F | | | G AND H) INFORMATION NOT SHOWN ON PLAN | | | 3) 1" PVC FRESH AIR LINE NOT SHOWN ON | | | HVAC PLAN AS STATED ON P-2 DETAIL 1-P-2 | | | 4) HORN AND STROBE REQUIRED FOR NOTIFI- | | | CATION OF FAN SHUT DOWN BY DUCT SMOKE | | | DETECTOR IF NOT TIED TO BLDG FIRE ALARM | | | PER NFPA 90A 1996 4-4.4.2 AND 4-4.4.3 |
|