| Plan Review Notes For Permit 99060989 |
| Permit Number |
99060989 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | COVER SHEET-HANDICAP BATHROOM REQS.SHALL | | | COMPLY W/FACBC.(SEE FIGURES 29 (A)(B). | | | | | | SUBMIT OCCUPANT LOAD OF BUILDING. | | | VERIFICATION BY OWNER REQD.PER TABLE 407 | | | 0F SPC. | | | | | | DRINKING FOUNTAINS ARE REQD.IN THE BAYS | | | PER SPC TABLE 407 AND SHALL COMPLY W/ | | | FACBC SEC.4.1.3.(10)(A). | | | | | | FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPC 409.4.1.1. | | | | | | SUBMIT A WATER ISOMETRIC FOR REVIEW PER | | | SPC 104.2.1. | | | | | | BREAKROOM SINK SHALL BE SHOWN ON THE | | | SANITARY ISOMETRIC.SPC 104.2.1. | | | | | | ALL TOILET ROOMS SHALL BE HANDICAP | | | ACCESSIBLE PER FACBC | | | SEC.4.1.3(11),FIGS.29 (A)(B). | | | | | | BREAKROOM SINK SHALL BE HANDICAP ACCESS- | | | IBLE PER FACBC PER FACBC SEC.4.24.1- | | | 4.24.7. | | | | | | WATER CLOSETS NOT PERMITTED ON WET VENTS | | | PER SEC 911.1.1,911.1.2. | | | ADDENDUM 10-23-99 PES | | | ADDRESS ALL COMMENTS ON PLAN REVIEW | | | DELETE OR VOID OLD REVISIONS SEC 104.2.1 | | | SUBMIT ELEVATIONS OF ALL H/C FIXTURES. | | | FIXTURE CLERANCE TO COMPLY WITH FACBC. | | | NO FACILITIES SHOWN FOR UNIT #2. | | | END OF COMMENTS |
|