| Plan Review Notes For Permit 99060902 |
| Permit Number |
99060902 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | | | | NEED TO SUBMIT PLAND WITH AIC RATING | | | DRAWN ON PANEL SCHED.215-5 | | | NOTE:OUTLET SPACING.210-52A | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:GROUNDING ELECTRODE CONDUCTOR | | | TO BLDG.STEEL ALSO. | | | NOTE:EQUIPMENT GROUNDING CONDUCTOR | | | REQ`D FROM MAIN DISC.TO PANEL. | | | ART`S 250-92/250-95 | | | | | | NEED THE ABOVE INFORMATION SUBMITTED | | | BEFORE ROUGH INSPECTION IS CALLED IN. |
|