| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-ENTRY DOORS CAN'T HAVE STORM PANELS |
| | BECAUSE THE MAIN EGRESS OF THE HOUSE |
| | WILL BE BLOCKED. REVISE INSTALLATION |
| | SCHEDULE AS REQUIRED. |
| | 2-ARCHITECT SPECIFIED GIRDER TRUSS AT |
| | FRONT PORCH. NEED TO SPECIFY UPLIFT |
| | CONNECTORS. |
| | *PROVIDE COMPLETE SPECIFICATIONS FOR |
| | DETAIL B-A6. SEE COMMENTS ON PLANS. |
| | *REVISE CONNECTOR C-A6 AS REQUIRED IN |
| | ORDER TO RESIST THE UPLIFT LOADS |
| | SPECIFIED IN ENGINEERED DRAWINGS. |
| | 3-ENGINEERED TRUSS LAYOUT DOES NOT SHOW |
| | GIRDER TRUSS AT FRONT PORCH SPECIFIED |
| | BY ARCHITECT. REVISE AS REQUIRED. |
| | *TRUSS DRAWINGS NEED TO BE UPDATED TO |
| | ASCE 7-95. |
| | CUT AND PASTED ENGINEERED TRUSS COPIES |
| | WILL NOT BE RECEIVED. ONLY ORIGINAL |
| | COPIES WITH ORIGINAL CALCULATIONS WILL |
| | BE ACCEPTED. |
| | 4-REVISE ORIGINAL DRAWINGS AS REQUIRED |
| | SHOWING THE CORRECTIONS/CLARIFICATIONS. |
| | 5-SLIDING GLASS DOORS: |
| | *USE ONLY THE REINFORCED DOORS IN ORDER |
| | TO MEET THE DESIGN PRESSURES SPECIFIED |
| | BY THE ARCHITECT. |
| | PROVIDE PRODUCT APPROVAL FOR SLIDING |
| | GLASS DOORS ASSEMBLY WITH TRANSOM ABOVE |
| | 6-MINIMUM CLEAR OPENING AT BEDROOM |
| | WINDOWS TO BE 5.0 S.F. AS PER SECTION |
| | 1005.4.4 SBC 1994. PROVIDE THE EXACT |
| | DIMENSIONS FOR WINDOWS AT BEDROOM #2 TO |
| | VERIFY CLEAR OPENING PRIOR TO |
| | INSTALLATION. |
| | 7-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| | DOORS PRIOR TO INSTALLATION. |
| | 8-GARAGE DOOR PRODUCT PRODUCT DOESN'T |
| | MEET THE DESIGN PRESSURES CALCULATED BY |
| | ARCHITECT. |