Plan Review Notes
Plan Review Notes For Permit 99060898
Permit Number 99060898
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-ENTRY DOORS CAN'T HAVE STORM PANELS
 BECAUSE THE MAIN EGRESS OF THE HOUSE
 WILL BE BLOCKED. REVISE INSTALLATION
 SCHEDULE AS REQUIRED.
 2-ARCHITECT SPECIFIED GIRDER TRUSS AT
 FRONT PORCH. NEED TO SPECIFY UPLIFT
 CONNECTORS.
 *PROVIDE COMPLETE SPECIFICATIONS FOR
 DETAIL B-A6. SEE COMMENTS ON PLANS.
 *REVISE CONNECTOR C-A6 AS REQUIRED IN
 ORDER TO RESIST THE UPLIFT LOADS
 SPECIFIED IN ENGINEERED DRAWINGS.
 3-ENGINEERED TRUSS LAYOUT DOES NOT SHOW
 GIRDER TRUSS AT FRONT PORCH SPECIFIED
 BY ARCHITECT. REVISE AS REQUIRED.
 *TRUSS DRAWINGS NEED TO BE UPDATED TO
 ASCE 7-95.
 CUT AND PASTED ENGINEERED TRUSS COPIES
 WILL NOT BE RECEIVED. ONLY ORIGINAL
 COPIES WITH ORIGINAL CALCULATIONS WILL
 BE ACCEPTED.
 4-REVISE ORIGINAL DRAWINGS AS REQUIRED
 SHOWING THE CORRECTIONS/CLARIFICATIONS.
 5-SLIDING GLASS DOORS:
 *USE ONLY THE REINFORCED DOORS IN ORDER
 TO MEET THE DESIGN PRESSURES SPECIFIED
 BY THE ARCHITECT.
 PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS ASSEMBLY WITH TRANSOM ABOVE
 6-MINIMUM CLEAR OPENING AT BEDROOM
 WINDOWS TO BE 5.0 S.F. AS PER SECTION
 1005.4.4 SBC 1994. PROVIDE THE EXACT
 DIMENSIONS FOR WINDOWS AT BEDROOM #2 TO
 VERIFY CLEAR OPENING PRIOR TO
 INSTALLATION.
 7-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS PRIOR TO INSTALLATION.
 8-GARAGE DOOR PRODUCT PRODUCT DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY
 ARCHITECT.