| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1*ARCHITECT SPECIFIED GIRDER TRUSS AT |
| | FRONT PORCH. PROVIDE COMPLETE DETAIL |
| | AND SPECIFY ALL CONNECTORS. |
| | *PROVIDE COMPLETE SPECIFICATIONS AND |
| | SIZES FOR FOR DETAIL B-6. |
| | *REVISE CONNECTOR C-A6 AS REQUIRED TO |
| | RESIST THE UPLIFT LOADS CALCULATED ON |
| | ENGINEERED TRUSSES. |
| | 2-ENGINEERED TRUSS LAYOUT DOESN'T SHOW |
| | GIRDER TRUSS AT FRONT PORCH. REVISE AND |
| | PROVIDE ENGINEERING AS REQUIRED. |
| | -TRUSS DRAWINGS NEED TO BE UPDATED TO |
| | ASCE 7-95. |
| | CUTTING, PASTING AND COPYING OF ALL |
| | ENGINEERED TRUSSES WILL NOT BE ACCEPTED |
| | 3-REVISE ALL ORIGINAL DRAWINGS SHOWING |
| | ALL CORRECTIONS/CLARIFICATIONS. |
| | 4-PROVIDE PRODUCT APPROVAL FOR SLIDING |
| | GLASS DOORS WITH TRANSOM ABOVE ASSEMBLY |
| | 5-MINIMUM CLEAR OPENING AT BEDROOM #2 TO |
| | BE 5 S.F. SEC. 1005.4.4 SBC 1997. |
| | PROVIDE THE EXACT DIMENSIONS FOR SUCH |
| | WINDOWS PRIOR TO INSTALLATION. |
| | 6-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| | DOORS PRIOR TO INSTALLATION. |
| | 7-GARAGE DOOR PRODUCT APPROVAL DOESN'T |
| | MEET THE DESIGN PRESSURES CALCULATED BY |
| | THE ARCHITECT. |