Plan Review Notes
Plan Review Notes For Permit 99060891
Permit Number 99060891
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************PROVISO******************
  
 NEED TO SUBMIT PLANS WITH AIC RATING
 DRAWN ON PANEL SCHED.ART.215-5
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:EQUIPMENT GROUNDING CONDUCTOR
 REQ`D FROM MAIN DISC.TO PANEL.
 ART.250-92/250-95
  
 NEED THE ABOVE INFORMATION SUBMITTED
 BEFORE ROUGH INSPECTION IS CALLED IN.