| Date |
Text |
| 2001-01-08 00:00:00 | ****************2ND.FLOOR*************** |
| | COMPLY W/ALL PREVIOUS COMMENTS DATED |
| | 7/13/99.(COMENTS HAVE NOT BEEN PROPERLY |
| | ADDRESSED.) |
| | |
| | THE OCCUPANT LOAD SHALL BE CLEARLY NOTED |
| | ON THE PLANS.SPC 104.2.1. |
| | |
| | WALLS AND FLOORS OF PUBLIC RESTROOMS |
| | SHALL COMPLY W/SBC 1204.2.(SUBMIT MANUF. |
| | SHEETS FOR SEMI-GLOSS PAINT TO ENSURE |
| | COMPLIANCE W/CODE FOR "NON-ABSORBENT" |
| | MATERIAL.) |
| | |
| | WATER HEATER SHALL BE READILY |
| | ACCESSIBLE PER SPC SEC 501.7, SEC.202 |
| | (DEFIN.)OF SBC.(SEE DEFIN.OF READILY |
| | ACCESIBLE.) |
| | |
| | PAN DRAIN AND RELIEF ARE STILL SHOWN AS |
| | BEING INTERCONNECTED.COMPLY W.SPC SEC. |
| | 507.8.4. |
| | |
| | CLEARLY SHOW DIMENSIONS(LXW)OF HANDICAP |
| | TOILET STALL ON THE PLANS.COMPLY W/ |
| | F.A.C.B.C. SEC.4.17.3.(SEE NEW |
| | CONSTRUCTION.-76" IS NOT WIDE ENOUGH.) |
| | |
| | DRINKING FOUNTAINS ARE NOT INDICATED ON |
| | THE PLBG.WATER OR SANITARY ISOMETTRICS. |
| | SHOW WATER SUPPLY CONTROL VALVES TO D.F. |
| | PER SPC 104.2.1. |
| | D.F'S ARE NOT SHOWN PLBG.FLOOR PLAN ON |
| | P-1. |
| | *****************3RD.FLOOR************** |
| | DRINKING FOUNTAIN IS REQ'D.PER TABLE 407 |
| | OF SPC. |
| | |
| | WALLS & FLOORS OF TOILET ROOMS SHALL BE |
| | NON-ABSORBENT MATERIAL PER SBC SEC. |
| | 1204.2(SUBMIT MANUF.SHEETS FOR PAINT.) |
| | |
| | FIXTURE CLEARANCE OF H.C.WATER CLOSET |
| | FROM WALL SHALL COMPLY W.F.A.C.B.C. SEC. |
| | 4.17.2, FIGS.30(A)(B). |
| | |
| | WATER HEATER SHALL BE READILY ACCESSIBLE |
| | PER SPC SEC.501.7, 202.(SEE DEFIN.OF |
| | READILY ACCESSIBLE.) |
| | |
| | PAN DRAIN AND RELIEF VALVE DRAIN SHALL |
| | NOT BE INTERCONNECTED PER STD.PLBG.CODE |
| | SEC.507.8.4. |
| | |
| | CLEARLY SHOW DIMENSIONS OF HANDICAP |
| | STALL ON PLANS.COMPLY W/F.A.C.B.C.SEC. |
| | 4.17.3-NEW CONSTRUCTION.(76" DOES NOT |
| | COMPLY.) |
| | |
| | SHOW HEIGHT OF SINK IN EMPLOYEE LOUNGE. |
| | COMPLY W/F.A.C.B.C. SECS.4.24.1- 4.24.7. |
| | (MAX.34" TO TOP OF CABINET.) |
| | |
| | FLOOR DRAINS SHALL NOT EXCEED DISTANCE |
| | FROM VENT AS SPECIFIED IN SPC TABLE 908. |
| | |
| | CLEARLY SHOW OCCUPANT LOAD ON PLANS. |
| | SPC 104.2.1. |