Plan Review Notes
Plan Review Notes For Permit 99060870
Permit Number 99060870
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD TO DETERMINE MIN.
 PLBG.FIXTURE REQ'S.PER STD.PLBG.CODE SEC
 407.1.3,TABLE 407.
  
 DRINKING FOUNTAIN IS REQ'D.PER TABLE 407
 OF STANDARD PLBG.CODE TABLE 407.
  
 WALLS &FLOORS OF TOILET ROOMS SHALL
 COMPLY W/STD.BLDG.CODE SEC.1204.2
  
 FIXTURE CLEARANCE OF H.C.WATER CLOSET
 FROM WALL SHALL COMPLY W/F.A.C.B.C.
 SEC.4.17.2 AND FIGS.30(A)(B)
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 FOR MAINTENANCE,SERVICING AND REPLACE-
 MENT PER STD.PLBG.CODE SEC.501.7, 202,
 (DEFIN.)AND SEC.507.8.
  
 PAN DRAIN AND RELIEFVALVE SHALL NOT BE
 INTERCONNECTED PER STD.PLBG.CODE SEC.
 507.8.4
  
 CLEARLY SHOW DIMENSIONS OF HANDICAP
 STALL ON ARCH.PLANS.COMPLY W/F.A.C.B.C.
 SSEC.4.17.3(SEE EXCEPION-NEW CONST.)
  
 EMPLOYEE LOUNGE SINK SHALL COMPLY
 W/F.A.C.B.C.SEC.4.24.1-4.24.7.(THE
 LOUNGE IS NOT CLASSED AS A WORK AREA.)
  
 FLOOR DRAINS SHALL NOT EXCEED DISTANCE
 FROM VENT AS SPECIFIED IN SPC TABLE 908.