| Plan Review Notes For Permit 99060870 |
| Permit Number |
99060870 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD TO DETERMINE MIN. | | | PLBG.FIXTURE REQ'S.PER STD.PLBG.CODE SEC | | | 407.1.3,TABLE 407. | | | | | | DRINKING FOUNTAIN IS REQ'D.PER TABLE 407 | | | OF STANDARD PLBG.CODE TABLE 407. | | | | | | WALLS &FLOORS OF TOILET ROOMS SHALL | | | COMPLY W/STD.BLDG.CODE SEC.1204.2 | | | | | | FIXTURE CLEARANCE OF H.C.WATER CLOSET | | | FROM WALL SHALL COMPLY W/F.A.C.B.C. | | | SEC.4.17.2 AND FIGS.30(A)(B) | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | FOR MAINTENANCE,SERVICING AND REPLACE- | | | MENT PER STD.PLBG.CODE SEC.501.7, 202, | | | (DEFIN.)AND SEC.507.8. | | | | | | PAN DRAIN AND RELIEFVALVE SHALL NOT BE | | | INTERCONNECTED PER STD.PLBG.CODE SEC. | | | 507.8.4 | | | | | | CLEARLY SHOW DIMENSIONS OF HANDICAP | | | STALL ON ARCH.PLANS.COMPLY W/F.A.C.B.C. | | | SSEC.4.17.3(SEE EXCEPION-NEW CONST.) | | | | | | EMPLOYEE LOUNGE SINK SHALL COMPLY | | | W/F.A.C.B.C.SEC.4.24.1-4.24.7.(THE | | | LOUNGE IS NOT CLASSED AS A WORK AREA.) | | | | | | FLOOR DRAINS SHALL NOT EXCEED DISTANCE | | | FROM VENT AS SPECIFIED IN SPC TABLE 908. |
|