2001-01-08 00:00:00*********DENIED*************************
  
 1) FIRE DAMPERS TO BE AT ALL RATED WALLS
 I.E. MECH RM 111AND 32X12 R/A OPENING
 ABOVE DOOR(112)
 2) DUCT DETECTOR IN RETURN AIR DUCT TO
 BE PRIOR TO ANY MIXING OF OUTSIDE AIR