| Plan Review Notes For Permit 99060864 |
| Permit Number |
99060864 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1-PAGE ESP2 FPL SHOWS A 1.25" RACEWAY | | | RISER SHOWS 2" RACEWAYWHICH ONE??? | | | | | | 2-LIGHTING CONTACTOR TO BE SERVICE RATED | | | | | | 3-NO MAIN SHOWN, IF LIGHTING CONTACTOR | | | IS TO BE USED THEN IT SHALL HAVE A | | | MANUAL OVERRIDE FOR A DISCONNECT | | | | | | 4-NO METER SHOWN, NOTE 2 STATES METER | | | BY OWNER? |
|