| 2001-01-08 00:00:00 | SHTS.C-9 & C-10.-CLEANOUTS IN BLDG. |
| | SEWERS SHALL BE INSTALLED AND COMPLY W/ |
| | STANDARD PLUMBING CODE SECS.710.2.4, |
| | 711.2.2,711.2.3. |
| | |
| | SHT.C-11.-SUMP DETAIL SHALL COMPLY W/ |
| | STD.PLBG.CODE SEC.717.2.(CONTINUATION |
| | F SUMP DISCHARGE IS SHOWN ON C-7,NOT |
| | C-4 AS NOTED.)CLARIFY SIZE OF DISCHARGE |
| | LINE.DETAIL SHOWS 6" & NOTE STATES 3". |
| | |
| | SHT.IR-4.-PLANS SHOW WATER SUPPLY FOR |
| | IRRIGATION SYSTEM FROM LAKE AND WELLS. |
| | SUBMIT COPY OF CONSUMPTIVE WATER USE |
| | PERMIT PER FLA.STATUTE 373.219. |
| | |
| | A WELL DRILLING PERMIT IS REQUIRED FROM |
| | SO.FLA.WATER MNGMT.DISTRICT FOR THE |
| | IRRIGATION WELLS PER FLA.STATUTE 373.342 |
| | |
| | SHT.P1.1-VACUUM BREAKERS AND GATE VALVES |
| | ARE REQ'D.ON POLE HYDRANTS PER STD.PLBG. |
| | CODE SEC.606.3.4.1.,610.4.1,610.4.2. |
| | |
| | SHT.P1.1-DETAIL #3-WATER SUPPLY CONTROL |
| | SHALL COMPLY W/STD.PLBG.CODE SEC.610.4 |
| | |
| | SHT.P1.1-WATER SUPPLY CONTROL FOR HOT |
| | WATER SHALL COMPLY W/STD.PLBG.CODE SEC. |
| | 610.4.1.(CLARIFY 3/4" LINE SUPPLYING 1") |
| | |
| | SHT.P1.2-DETAIL#3-VENT SIZING DOESN'T |
| | COMPLY W/TABLE 920.2 OF STD.PLBG.CODE. |
| | (ALSO APPLIES TO SHT.1.1 DETAIL #2.) |
| | |
| | MIN.SIZE U/G DRAINAGE PIPE SHALL BE 2" |
| | PER STD.PLBG.CODE SEC.714.4 (SEE EEW ON |
| | SHT.P1.2 DETAIL#3). |
| | |
| | SUBMIT DETAIL OF INTERCEPTOR.COMPLY W/ |
| | STD.PLBG.CODE SEC.1004. |
| | |
| | SUBMIT STORM/ROOF DRAINAGE RISER DIAGRAM |
| | INDICATE SQ.FOOTAGE DRAINED BY EA.DRAIN. |
| | COMPLY W/STD.PLBG.CODE SEC.1108,1109. |
| | |
| | INSTALLATION OF TRAP PRIMING DEVICES |
| | SHALL COMPLY W/STD.PLBG.CODE SEC.614.4.6 |
| | |
| | SHT.P2.0-DETAIL#10.-FLOOR DRAIN IN PUMP |
| | ROOM IS NOT VENTED.COMPLY W/STD.PLBG. |
| | CODE SEC.908.1 |
| | |
| | ROOF FAUCETS SHALL BE VALVED PER STD. |
| | PLBG.CODE SEC.610.4.1. |