| Plan Review Notes For Permit 99060720 |
| Permit Number |
99060720 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | THIS PLAN REVIEW WAS FOR THE EXIT STAIRS | | | PLANNED FOR THE SOUTH SIDE OF THE | | | BUILDING. | | | | | | 1) PLEASE PROVIDE DETAILS ON FIRE RATED | | | WINDOWS AND FRAMES TO THIS OFFICE. | | | 2) STAIRS ARE TO BE SLIP RESISTANT. | | | 3) STAIRS TO MEET ALL OF THE | | | REQUIREMENTS FOR NEW STAIRS PER NFPA | | | 101, THE LIFE SAFETY CODE, 1985 | | | EDITION. THE STAIRS ARE ALLOWED TO BE | | | 36" WIDE BASED ON OCCUPANT LOADS OF | | | LESS THAN 50 PERSONS. | | | 4) PLEASE SUBMIT SHOP DRAWINGS FOR THE | | | STAIRS. | | | 5) ANY AND ALL OPENINGS WITHIN 10 FEET | | | OF THE STAIRS ARE TO BE PROTECTED BY | | | FIRE RATED WINDOWS AND DOORS. | | | 6) HOW IS STAIR SUPPORTED AND FASTENED | | | TO THE BUILDING. | | | 7) HANDRAILS AND GUARDS TO COMPLY WITH | | | NFPA 101, THE LIFE SAFETY CODE,1985 | | | EDITION. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|