Plan Review Notes
Plan Review Notes For Permit 99060695
Permit Number 99060695
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00UNSAT #500
 SHT M.1 PLUMBING PLAN NOTES
 (1) NOTE 3 WATER RISER ISOMETRIC WITH
 PIPE SIZES.SEC 104.2
 (2) NOTE 4 WTR HTR TO BE READLY
 ACCESSIBLE. SEC 501.7 LOCATION
 (3) NOTE 4 DRAIN PAN 1",RUN OUTSIDE OR
 SUITABLE INDIRECT WASTE RECEPTOR
 SEC 507.8.3
 (4) NOTE 4 DIELECTRIC UNIONS: PROHIBITED
 USE DIELECTRIC COUPLINGS OR NIPPLES.
 SEC 603-MATERIALS
 (5) NOTE 8 TP & DRAIN PAN TERMINATION:
 RUN OUTSIDE OR SUITABLE WASTE RECEPTOR.
 SEC 507.8.3
 END OF COMMENTS