2001-01-08 00:00:00****************DENIED******************
  
 1) OUTSIDE AIR CALCULATIONS REQUIRED PER
 ASHRAE 62-89
 2) OUTSIDE AIR ON M-2 =450CFM M-3 = 300
 CFMCAN UNIT SPECIFIED DO 450CFM O/A?
 3) CONDENSATE DRAIN SHALL TERMINATE IN
 STORM SEWER OR FRENCH DRAIN, NOT SANI-
 TARY SEWER
 4) BACKROOM WITH 400 CFM SHALL RETURN
 AIR PATH TO RETURN AIR OF AHU-1