| Plan Review Notes For Permit 99060624 |
| Permit Number |
99060624 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | | | | 1) OUTSIDE AIR CALCULATIONS REQUIRED PER | | | ASHRAE 62-89 | | | 2) OUTSIDE AIR ON M-2 =450CFM M-3 = 300 | | | CFMCAN UNIT SPECIFIED DO 450CFM O/A? | | | 3) CONDENSATE DRAIN SHALL TERMINATE IN | | | STORM SEWER OR FRENCH DRAIN, NOT SANI- | | | TARY SEWER | | | 4) BACKROOM WITH 400 CFM SHALL RETURN | | | AIR PATH TO RETURN AIR OF AHU-1 |
|