| Plan Review Notes For Permit 99060289 |
| Permit Number |
99060289 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************* | | | | | | NEED TO SUBMIT FAULT CURRENT CACULATIONS | | | AND HAVE AIC RATING DRAWN ON PANEL SCHD. | | | ART.215-5 | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:ALL RECEPTS.SERVING KITCHEN | | | COUNTER ARE TO BE GFI/GFI PROTECTED. | | | ART.210-8-A-6 | | | NOTE:GROUNDIG ELECTRODE CONDUCTOR | | | TO GRND. ROD,BLDG.STEEL. | | | | | | NEED TO HAVE ABOVE INFORMATION BEFORE | | | ROUGH INSPECTION. |
|