| Plan Review Notes For Permit 99060267 |
| Permit Number |
99060267 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | | | | NOTE:RECEPTS.SERVING KITCHEN COUNTER- | | | SPACE ARE TO BE GFI/GFI PROTECTED. | | | ART21-8-A-6 | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:GFI RECEPTS.REQ`D FRONT OF HOUSE | | | ART.210-52E | | | NOTE:RECEPT.REQ`D FOR A/C EQUIPMENT. | | | ART.210-63 | | | NEED TO SUBMIT FAULT CURRENT/AIC | | | RATING.TO BE LISTED ON PANEL SCHED. | | | ART.215-5 | | | NOTE:GROUNDING ELECTRODE CONDUCTOR | | | TO BLDG. STEEL ALSO. | | | | | | NEED THE ABOVE DRAWN ON PLANS AND | | | SUBMITTED BEFORE ROUGH INSPECTION. |
|