Plan Review Notes
Plan Review Notes For Permit 99060267
Permit Number 99060267
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO*******************
  
 NOTE:RECEPTS.SERVING KITCHEN COUNTER-
 SPACE ARE TO BE GFI/GFI PROTECTED.
 ART21-8-A-6
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:GFI RECEPTS.REQ`D FRONT OF HOUSE
 ART.210-52E
 NOTE:RECEPT.REQ`D FOR A/C EQUIPMENT.
 ART.210-63
 NEED TO SUBMIT FAULT CURRENT/AIC
 RATING.TO BE LISTED ON PANEL SCHED.
 ART.215-5
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 TO BLDG. STEEL ALSO.
  
 NEED THE ABOVE DRAWN ON PLANS AND
 SUBMITTED BEFORE ROUGH INSPECTION.