2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE:NEED TO SUBMIT AIC RATING FROM
 FAULT CURRENTCALCULATIONS.110-9/215-5
 2)NOTE:SMOKE DETECTORS REQ`D INSIDE
 AND OUTSIDE BEDROOMS NFPA-72
 3)NOTE:KITCHEN RECEPT.210-52C
 4)NOTE:GFI RECEPT.REQ`D AT C/UNIT
 ART,210-63
 5)NOTE:RECEPT.FOR JACUZZI TO BE GFI AND
 ACCESSIBLE.
 6)NOTE:OTHER MISSING OUTLETS AS PER
 ART;210-52
 7)NOTE:GROUNDING ELECTRODE CONDUCTOR
 TO GO TO BLDG.STEEL ALSO.
 8)NOTE:PLANS SHOW MAIN DISC.WITH METER
 AT SIDE OF HOUSE BUT NOT ON RISER
 DIAGRAM???
  
 NEED ALL THE ABOVE SUBMITTED AND
 APPROVED BEFORE ROUGH ELECTRICAL
 INSPECTION.