| Plan Review Notes For Permit 99060262 |
| Permit Number |
99060262 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | | | | 1)NOTE:NEED TO SUBMIT AIC RATING FROM | | | FAULT CURRENTCALCULATIONS.110-9/215-5 | | | 2)NOTE:SMOKE DETECTORS REQ`D INSIDE | | | AND OUTSIDE BEDROOMS NFPA-72 | | | 3)NOTE:KITCHEN RECEPT.210-52C | | | 4)NOTE:GFI RECEPT.REQ`D AT C/UNIT | | | ART,210-63 | | | 5)NOTE:RECEPT.FOR JACUZZI TO BE GFI AND | | | ACCESSIBLE. | | | 6)NOTE:OTHER MISSING OUTLETS AS PER | | | ART;210-52 | | | 7)NOTE:GROUNDING ELECTRODE CONDUCTOR | | | TO GO TO BLDG.STEEL ALSO. | | | 8)NOTE:PLANS SHOW MAIN DISC.WITH METER | | | AT SIDE OF HOUSE BUT NOT ON RISER | | | DIAGRAM??? | | | | | | NEED ALL THE ABOVE SUBMITTED AND | | | APPROVED BEFORE ROUGH ELECTRICAL | | | INSPECTION. |
|