Plan Review Notes
Plan Review Notes For Permit 99051251
Permit Number 99051251
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00MAX.OF 4 FIXTURE UNITS PERMITTED ON 2"
 WET VENT.(MASTER BATH). STANDARD PLBG.
 CODE SEC.911.1(1).
  
 BIDET DOWNSTREAM OF W.C. SHALL BE VENTED
 SPC SEC.913.2.
  
 WASHING MACHINE NOT PERMITTED ON 2"
 CROSS PER SPC SEC.409.12.3.
  
 11/10 APPROVED 9/28 BY T LARGE SIGNED
 APPLICATIONJC