Plan Review Notes
Plan Review Notes For Permit 99051250
Permit Number 99051250
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00BIDET DOWNSTREAM OF WATER CLOSET SHALL
 BE VENTED PER SPC 913.2
  
 MAX.2 WATER CLOSETS PERMITTED ON 3" BLDG
 DRAIN. SPC TABLE 714.1,FOOTNOTE #3.
  
 LAYOUT OF FIXTURES ON SANITARY RISER
 DOESN'T CORRELATE W/FLOOR PLAN. SPC SEC.
 104.2.1.