Plan Review Notes
Plan Review Notes For Permit 99051241
Permit Number 99051241
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00OK`D 7/19/99*DENIED*******************
  
 NEED TO SUBMIT LOAD CACULATIONS FOR
 EXISTING SERVICE.ART.220-3-D-1
 PLEASE SHOW RISER DIAGRAM WITH METER,
 PANEL,WIRE SIZES.
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:OUTLET SPACING 210-52A
 NOTE:EXISTING PANEL MUST HAVE SUFFICENT
 SPACE TO SERVE NEW CIRCUTS INCLUDING
 ART.21-52D BATH RECEPTS.ON 20A CIRCUT.
  
 NEED TO RESUBMIT
  
 OK`D 7/19/99