Plan Review Notes
Plan Review Notes For Permit 99051209
Permit Number 99051209
Review Stop E
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00************ UNSAT ********************
  
 1) NOTE: NEED PLANS USED FOR FINAL TO
 HAVE ALL CODECORRECTIONS DONE AND ALL
 ASBUILTS SUBMITTED ON PLANS. 215-5
  
 2) NOTE: SMOKE DETECTORS INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS AS REQ`D BY
 1993/1996 NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE INCLUDE BOTH PANEL SCHED-
 ULES TO IN BATH(S) CIRCUT(S) AS REQ`D
 BY210-52D/215-5
  
 4)NOTE: PLEAS EHAVE AIC RATING LISTED
 ON THE TOP OF PANEL SCHEDULES.230-65/
 110-9/215-5
  
 PLEASE HAVE THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 FINAL ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
 659-8096 EXT 8372